3. Product features

The controller described in this manual is a centralized controller that can be operated over the Web.
Any connected air conditioning systems can be operated or monitored directly from the controller or over the Web using
browser software.
Refer to the Web browser operation manual (separate volume) for how to use this functions.
Function
Indoor unit, Ventilation unit
(LOSSNAY and OA handling unit),
DIDO controller, Air To Water
(PWFY), HWHP (CAHV)
Number of units in one group
(indoor, independent OA
processing unit, or LOSSNAY,
Number of
HWHP (CAHV))
controlled unit
Number of remote controllers in
one group
Number of system controllers in
one group
Number of interlocked LOSSNAY
units
ON/OFF
Operation mode
Fan speed
Temperature setting
Operation
*1
*7
Air direction and swing operation
Fan mode (HWHP (CAHV))
Operating/stopping interlocked
LOSSNAY units
Schedule*5
Schedule
Available/Not Available
Prohibit local remote control
Filter sign reset
Water circuit sign reset
(Air To Water (PWFY))
Error reset
Error history reset
Up to 150 units are connectable (including the interlocked units) *2
By connecting three PAC-YG50ECA Expansion controllers (sold separately), a maximum of 150
units of equipments can be controlled. Each DIDO controller (PAC-YG66DCA) contact counts as
one unit.*4
1-16 units (Indoor unit, independent OA processing unit, ventilation system (LOSSNAY), and DIDO
controller cannot be registered to the same group.) *6
1-2
0-4 (including the number of remote controller in one group)
• Number of LOSSNAY units that can be interlocked with an indoor unit: 1
• Number of indoor units that can be interlocked with a LOSSNAY unit: 16
The ON/OFF operation can be performed as a collective, per group, or per block.
The switch operation for the operation mode setting can be performed as a collective, per group,
per block, per floor, or per building. (Available modes depend on the model of indoor units.)
[Selectable operation mode for the indoor unit]
COOL/DRY/FAN/AUTO/HEAT
[Selectable operation mode for the independent ventilation]
HEAT RECOVERY/BY-PASS/AUTO
[Selectable operation mode for Air To Water (PWFY) and HWHP (CAHV)]
HEATING/HEATING ECO/HOT WATER/ANTI-FREEZE
COOLING (for Air To Water (PWFY))
Up to four fan speeds are available. Fan speed can be changed collectively, or for each group or
block of indoor units. (The number of available fan speeds depends on the indoor model (2 speeds,
3 speeds, 4 speeds, and Auto). "Auto" is available only on the models that support that function.)
Temperature setting can be performed collectively, per group, or per block.
[Setting temperature range for air conditioner]
Cool (Dry) operation:
19 ~ 30°C / 67 ~ 87°F
Heat operation:
17 ~ 28°C / 63 ~ 83°F
Auto operation:
19 ~ 28°C / 67 ~ 83°F
[Setting temperature range for Air To Water (PWFY)]
*3
[Booster unit]
Heating:
30 ~ 50°C/87 ~ 122°F
Heating ECO: 30 ~ 45°C/87 ~ 113°F
Hot Water:
30 ~ 70°C/87 ~ 158°F
Anti-freeze:
10 ~ 45°C/50 ~ 113°F
Cooling:
Invalid
[Setting temperature for HWHP (CAHV)]
Heating:
25 ~ 70°C/77 ~ 158°F
Heating ECO: Invalid
Hot Water:
25 ~ 70°C/77 ~ 158°F
Anti-freeze:
Invalid
Vertical air flow directions (5 directions), auto setting, and swing setting can be changed collectively,
or for each group or block of indoor units. (Available air flow directions depend on the model. [5 air
flow directions and AUTO] are available only on the models that support those settings.
The fan mode of HWHP (CAHV) units can be switched between Normal and Snow.
Interlocked LOSSNAY units (if any) can be operated (at High or Low) or stopped collectively or for
each group or block of indoor units. (Ventilation mode cannot be selected for the interlocked
LOSSNAY units.)
Group is the smallest unit to which a weekly schedule can be assigned. The same schedule can be
applied collectively, or to each group, groups in a block, or groups on a floor.
• Up to 24 events can be scheduled for each day.
• "ON/OFF", "Operation mode", "Temperature Setting", "Fan Speed Setting", "Vane Setting", and
"Prohibition of operation from local remote controller" can be timer-controlled.
If a license is registered
• Five types of weekly schedule patterns are available.
• Five operation patterns (A-E) can be set for each year, up to 50 days can be allocated to each
pattern.
• When Optimized startup schedule is set, the operation starts so that the preset temperature is
reached at the preset time. (Applicable to indoor units only)
Schedule settings can be Available or Not Available for each group, block, floor, or for all units
collectively.
Operation of certain functions from the local remote controllers can be prohibited collectively or for
each group or blocks of indoor units.
(Applicable functions: ON/OFF, operation mode, temperature setting, filter sign, Water circuit sign
(Air To Water (PWFY)))
Filter sign can be reset for each group or block of indoor units.
Water circuit sign (Air To Water (PWFY)) can be reset for each group or block of indoor units.
Resets the display of error.
Resets the error history (unit error, communication error).
– 3 –
Description
*3
[Water HEX unit]
Heating:
30 ~ 45°C/87 ~ 113°F
Heating ECO: 30 ~ 45°C/87 ~ 113°F
Hot Water:
Invalid
Anti-freeze:
10 ~ 45°C/50 ~ 113°F
Cooling:
10 ~ 30°C/50 ~ 87°F