Mitsubishi Electric AG-150A Instruction Book page 22

Air-conditioner control system centralized controller
Hide thumbs Also See for AG-150A:
Table of Contents

Advertisement

(10) Make the settings for the Expansion controller IP
address, M-NET, and external input.
(11) Make the settings for the group names and unit
addresses.
(12) Make the settings for the interlocked LOSSNAY units.
(10) Make the settings for the Expansion controller IP
address.
• Touch "Save Settings" to confirm that the settings for the M-
NET and external input are the same as the ones made for
the first unit (master).
• After setting the IP address, a screen that indicates that the
connection information of Expansion controllers is being
collected will be displayed for a few minutes.
(11) Make the settings for the general equipment and group
name.
A group name different from the first unit (master) may be
assigned.
Check that the group settings are the same as the ones made for
the first unit (master).
Re-enter the same settings for the general equipment as the ones
for the first unit (master).
(12) Confirm the settings for the interlocked LOSSNAY
units.
Check that the interlocked LOSSNAY settings are the same
as the ones made for the first unit (master).
– 21 –