Mitsubishi Electric AG-150A-A Installation Manual

Mitsubishi Electric AG-150A-A Installation Manual

Air-conditioner control system
Hide thumbs Also See for AG-150A-A:

Advertisement

Quick Links

Air-conditioner Control System
Centralized Controller
AG-150A
AG-150A-A
Before installing the controller, please read this Installation Manual carefully to ensure
proper operation. Retain this manual for future reference.
Installation Manual
Contents
1. Safety Precautions ..................................................1
2. Parts List .................................................................2
3. External Dimensions ...............................................3
4. Product Features.....................................................4
1. Specification......................................................4
2. Parts names and functions ...............................4
5. System Diagram......................................................6
equipments) ..................................................6
2. System with connection to an Expansion
6. Installation .............................................................10
1. Field-supplied Parts ........................................10
2. Installation.......................................................10
7. Wiring ....................................................................21
Expansion controller .....................................21
Expansion controller ...................................22
8. Initial Setting..........................................................23
9. Test Run................................................................24
10. System Configuration Example.............................25
Expansion controller ...................................25
3. To control a Mr. Slim.......................................25
4. To control a K control model ...........................25
11. External input/output usage ..................................26
1. External signal input function ..........................26
2. External signal output function........................27
12. LAN connection function .......................................28
13. Optional Accessories ............................................29

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric AG-150A-A

  • Page 1: Table Of Contents

    Air-conditioner Control System Centralized Controller AG-150A AG-150A-A Installation Manual Contents 1. Safety Precautions ..........1 2. Parts List ..............2 3. External Dimensions ..........3 4. Product Features.............4 1. Specification............4 2. Parts names and functions .......4 5. System Diagram............6 1. Standard configuration (using the AG-150A to control a system with 50 or fewer units of equipments) ..........6...
  • Page 2: Safety Precautions

    The backlight (fluorescent lamp) of the liquid crystal Use a security device such as a VPN router when display module contains a minute amount of mercury, connecting the AG-150A, AG-150A-A to the Internet to which is harmful to the environment. prevent unauthorized access.
  • Page 3: Parts List

    Up to three Expansion controllers can be connected to a system, each of which can control up to 50 units of equipments. To control 50 or more units of equipments, use AG-150A, AG-150A-A software version 2.10 or later. Hereinafter, Centralized controller AG-150A, AG-150A-A, unless otherwise specified, will be called "AG-150A".
  • Page 4: External Dimensions

    3 External Dimensions Unit: mm (in) 25.6 ( - / 44.7 ( - 300 ( - 272 ( 0- Back View 272 (10- 250 (9- A type installation plate B type installation plate Unit: mm (in) 300 (11- 290.8 (11- 278 (10- 273 (10- 250 (9-...
  • Page 5: Product Features

    4 Product Features AG-150A is a centralized controller that features advanced functions such as the Web function. Air conditioning units connected to this controller can be operated or monitored directly from this controller or over the Web by purchasing a license, using a browser software on the computer. Up to 50 indoor units and general equipment can be monitored and operated from an AG-150A unit.
  • Page 6 Left view USB storage device Connects to a USB storage device to copy and read data from the AG-150A Back View Unused Unused Connects to other units of equipments over the LAN via a switching HUB. Connects to the power cable when the mounting attachment A type Connects to PAC-YG10HA (PAC-YG85KTB;...
  • Page 7: System Diagram

    5 System Diagram 1. Standard configuration (using the AG-150A to control a system with 50 or fewer units of equipments) POWER (24VDC) Indoor unit Centralized controller Power supply unit (optional) Local remote controller Model:AG-150A Model: PAC-SC51KUA M-NET transmission line K transmission line M-NET MA remote controller line M-NET...
  • Page 8 NOTES * Apply following precautions when using the K transmission converter (model PAC-SC25KAA; discontinued) and controlling the M-NET model and K control model with the same controller. Refer to the K transmission converter (PAC-SC25KAA) installation manual for details. 1 Centralized controller address Always set the controller address to “000”.
  • Page 9: Controller (System With 50 Or More Units)

    2. System with connection to an Expansion controller (system with 51 or more units) Power supply (DC24V) Indoor unit *1: M-NET terminals will not be used. Local remote Centralized controller *2: Terminal block TB2 will not be used. Power supply unit (sold separately) Model name: AG-150A * controller Model name: PAC-SC51KUA *...
  • Page 10 NOTES * Up to three PAC-YG50ECA controllers can be connected to each AG-150A unit. * Main system controllers (e.g., AG-150A) cannot be connected to an M-NET system that is controlled by an Expansion controller. * Main and sub system controllers (M-NET) AG-150A is for exclusive use as a main SC.
  • Page 11: Installation

    6 Installation CAUTION * Install and wire the unit with the power to the power supply unit (PAC-SC51KUA) turned off. * Do not put the signal wire and power wire in the same conduit. * When routing the cable from the top of the controller, let the cable hang down below the connector before connecting it to the terminal block or connector as shown in the figure below to prevent water from running down the cable and causing electric shock or fire.
  • Page 12 By installing the centralized controller and a power supply unit Wall (PAC-SC51KUA; sold separately) inside the mounting AG-150A attachment on the wall. PAC-YG85KTB (sold Mounting attachment A type (PAC-YG85KTB; sold separately) separately) is required is required. in wall mount installation with both the controller and a power supply unit.
  • Page 13 4 Attach the A type installation plate (supplied) to the B type Inside the wall M4 flathead screw installation plate (supplied) with the M4 flathead screws (supplied) (supplied), sandwiching the wall between the two plates. Prior to installation, check that the wall is strong enough to support the weight of the controller to prevent the controller B type Installation plate A type Installation plate...
  • Page 14 7 Attach the controller to the A type installation plate with the M4 roundhead screws (supplied). A type Installation plate (supplied) M4 roundhead screw (supplied) 8 Replace the AG-150A surface cover. 2-2. Wall-Embedded installation with an Electric box (PAC-YG83UTB; sold separately) 1 Ensure there is enough space to install the controller as shown below.
  • Page 15 4 Cut out an opening in the wall as shown in the shaded area in the figure below. (Width × Height: 278 mm (11 in) × 152 mm (6 in)) Follow the dimensions in the figure exactly. If the opening is too large, it will be hard to properly install the unit. Make A-type mounting plate screw holes on the hole as shown in the right figure.
  • Page 16 Back of controller shield M-NET transmission cable DC power cable Function earthing DC power cable * When a PAC-YG50ECA Expansion controller is used, (ground) cable the M-NET terminals will not be used. M-NET transmission cable * When using bridge wiring of the shield, use the S-terminal as shown below.
  • Page 17 2 Punch out the appropriate knockout hole, depending on how Knockout hole the wiring is routed. 3 Sand the cut surface of the knockout hole smooth. CAUTION * Any rough edges that are left may damage the cable and cause electric shock or fire. 4 Push the M-NET transmission cable, DC power cable through the knockout hole.
  • Page 18 2-4. Installing the centralized controller and a power supply unit (PAC-SC51KUA; sold separately) inside the mounting attachment A type (PAC-YG85KTB; sold separately) on the wall 1 Ensure there is enough space to install the controller as Unit: mm (in) 30 (1- shown in the figure at right.
  • Page 19 0 Connect the wiring from the power supply unit to the centralized controller. DC power cable M-NET (supplied with PAC- transmission cable YG85KTB) (supplied with PAC-YG85KTB) DC power cable NOTE (supplied with M-NET transmission cable PAC-YG85KTB) * When using an LAN and external signal (supplied with PAC-YG85KTB) I/O, refer to section 11 External input/output usage .
  • Page 20 2-5. Installing the centralized controller on the control board 1 Make sure that there is an adequate amount of space to Unit: mm (in) install the controller as shown in the figure on the right. 30 (1- 300 (11- Control board NOTES * When installing two or more controllers side-by-side and horizontally ensure that there is at least 130 mm (5- in) or more...
  • Page 21 7 Screw down the A type installation plate (supplied) on the Unit: mm (in) control board door with the M4 flathead screws (supplied). φ 4 or above Drill four screw holes and a 278 mm [W] × 152 mm [H] hole 278 (10- on the control board door ahead of time.
  • Page 22: Wiring

    7 Wiring 1. System without connection to a PAC-YG50ECA Expansion controller Power supply unit (PAC-SC51KUA) Centralized controller AG-150A (Front view) Outdoor unit Cable clamp M-NET transmission line (Centralized control line) DC power supply line (24VDC) *Polarized Power supply unit Centralized controller (Back view) M-NET Output V- FG...
  • Page 23: System With Connection To A Pac-Yg50Eca Expansion Controller

    2. System with connection to a PAC-YG50ECA Expansion controller Power supply unit (PAC-SC51KUA) Centralized controller AG-150A (Front view) Cable clamp Switching HUB PAC-YG50ECA M-NET DC power supply line (24VDC) Outdoor unit * Polarized Power supply unit Centralized controller (Back view) M-NET Output V- FG...
  • Page 24: Initial Setting

    8 Initial Setting NOTES * Choose from two initial setting methods: 1) Making the settings via AG-150A, 2) Making the setting via the LAN using the Initial Setting Web. • This manual provides the instructions on making the initial settings from AG-150A. •...
  • Page 25: Test Run

    9 Test Run • Before performing a test run, verify that the group setting has been performed and the startup sequence for the interlocked operation setting has been completed. • It may take approximately 5 minutes from power on until the local remote controller becomes operable. Test run procedure 1 Turn the AG-150A and all air conditioning units on.
  • Page 26: System Configuration Example

    10 System Configuration Example 1. System with connection to a PAC-YG50ECA Expansion controller : IP address Expansion controller : M-NET address M-NET (PAC-YG50ECA) AG-150A Indoor units: 50 units 192.168.1.211 192.168.1.1 ON/OFF remote controller etc. 24VDC M-NET adapter Indoor unit: 20 units Switching Expansion controller Indoor unit address 01 ~ 20...
  • Page 27: External Input/Output Usage

    11 External input/output usage 1. External signal input function * External signal input requires the external I/O adapter (PAC-YG10HA) sold separately. NOTES * When using a PAC-YG50ECA Expansion controller, connect the external input/output adapter to the external input terminal on the Expansion controller, not to the AG-150A.
  • Page 28: External Signal Output Function

    (4) Recommended circuit (A) For level signal Use relays X1, X2, Y1, and Y2 that meet the following specifications. Contact rating Rated voltage >=12VDC Run/stop or Rated current >= 0.1A Emergency stop Minimum applicable load =< 1mA at DC Important Orange Power supply •...
  • Page 29: Lan Connection Function

    NOTE Punch out the knockout hole • When connecting the external input/output cables to connector CN5 on the controller, punch out the knockout hole. 12 LAN connection function When using the LAN connection function, insert the LAN cable to the LAN connector of the controller. * Connect the LAN cable from the AG-150A to other equipments via a switching HUB.
  • Page 30: Optional Accessories

    13 Optional Accessories Parts Model Usage Note Supplies power to the controller and M-NET Power supply unit PAC-SC51KUA transmission line. Each Expansion controller can control up to 50 units. Enables the connection of up to 150 indoor and Expansion controller PAC-YG50ECA (Up to three Expansion LOSSNAY units to an AG-150A.
  • Page 32 Please be sure to put the contact address/telephone number on this manual before handing it to the customer. HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN Authorized representative in EU:MITSUBISHI ELECTRIC EUROPE B.V. HARMAN HOUSE, 1 GEORGE STREET, UXBRIDGE, MIDDLESEX UB8 1QQ, U.K. WT05368X08...
  • Page 33 Related Links Model Number: AG150 Controls Brochure Garfield House, London Kingsmills Hotel, Scotland AG150 Instruction Book Web User (WT05492X13) AG150 Instruction Book Web Maintenance (WT05490X14) AG150 Instruction Book Web Initial (WT05491X14) AG150 Instruction Book (WT05369X15) AG150 Installation Manual (WT05368X08) AG150 Declaration of Conformity EUT10014A...

This manual is also suitable for:

Ag-150a