Procedure
The procedure for calibrating the auxiliary output is listed in Table 6-2. The numeric
codes are also listed.
Make sure "LOCK" in the Lock Set Up group is set to "NONE" (see Subsection 3.4).
Step
Operation
Enter Calibration
1
Mode
Calibrate 0 %
2
3
Calibrate 100 %
4
Exit the
Calibration Mode
Table 6-2 Auxiliary Output Calibration Procedure
Press
Upper Display = CAL
SET UP
Lower Display = AUXOUT
until you see
You will see:
FUNCTION
Upper Display = A Value
Lower Display = ZROVAL
until the desired 0 % output is read on the milliammeter,
or
use the values shown below depending on the action of
your controller.
To store the 0 % value you will see:
FUNCTION
Upper Display = A Value
Lower Display = SPNVAL
until the desired 100 % output is read on the milliammeter.
or
The controller stores the span value.
FUNCTION
To exit the calibration mode.
LOWER
DISPLAY
UDC2500 Universal Digital Limit ControllerProduct Manual
Output Calibration
Result
71