Technical Data Actuator Controls - AUMA SA 07.2 Operation Instructions Manual

Multi-turn actuators with actuator controls auma matic basic amb 01.1/amb02.1
Hide thumbs Also See for SA 07.2:
Table of Contents

Advertisement

SA 07.2
SA 16.2/SAR 07.2
AMB 01.1/AMB02.1
13.2.

Technical data Actuator controls

Features and functions
Mains voltage, mains frequency
Overvoltage category
Rated power
Switchgear
Control
Status signals
Voltage output
Local controls
SAR 16.2
Refer to name plates at controls and motor
Permissible variation of the mains voltage: ±10 %
Permissible variation of the mains frequency: ±5 %
Current consumption of controls depending on mains voltage:
100 to 120 V AC = max. 575 mA
208 to 240 V AC = max. 275 mA
380 to 690 V AC = max. 160 mA
Category III according to IEC 60364-4-443
The controls are designed for the rated motor power, refer to motor name plate
Standard:
Reversing contactors (mechanically and electrically interlocked) for AUMA power
classes A1/A2
Options:
Reversing contactors (mechanically and electrically interlocked) for AUMA power
classes A1/A2 with additional contacts, 1 NC + 1 NO each
Reversing contactors (mechanically and electrically interlocked) for AUMA power
class A3
Reversing contactors are designed for a lifetime of 2 million starts.
For the assignment of AUMA power classes, please refer to Electrical data Multi-turn actuat-
ors/Part-turn actuators.
Standard:
Control inputs OPEN - STOP - CLOSE, 230 V AC, internally supplied (non po-
tential-free)
EMERGENCY-STOP function from control room, independent of position of
selector switch
Option:
Control inputs , OPEN - STOP - CLOSE, 24 V DC, externally supplied (with
galvanic isolation via contact), current consumption: approx. 15 mA per input
Control inputs OPEN - STOP - CLOSE, 24 V DC, internally supplied (non poten-
tial-free)
Control inputs OPEN - STOP - CLOSE, 115 V AC, internally supplied (non po-
tential-free)
Standard:
Output signals for end positions OPEN/CLOSED, 230 V AC, internally supplied
(non potential-free) for external indication lights OPEN/CLOSE (P
Options:
5 potential-free output signals with one common, max. 250 V AC, 2 A (res-
istive load)
-
Motor protection tripped (thermal fault)
-
Torque fault
-
No torque fault
Selector switch position LOCAL/REMOTE
Standard:
230 V AC ±10 %, max. 2.5 W for supply of the control inputs., galvanically isol-
ated from internal voltage supply
Option:
24 V DC ±5 %, max. 10 mA for supply of the control inputs, galvanically isolated
from internal voltage supply
115 V AC ±10 %, max. 30 mA for supply of the control inputs, galvanically isol-
ated from internal voltage supply
Standard:
Selector switch LOCAL - OFF - REMOTE (lockable in all three positions)
Push buttons OPEN, STOP, CLOSE
2 indication lights: End position CLOSED (yellow), end position OPEN (green)
Options:
3 indication lights: End position CLOSED (yellow), collective fault signal (red),
end position OPEN (green)
Special colours for the indication lights
Protection cover, lockable
Technical data
= 2.5 W)
max
55