Commissioning (basic settings)
9.5.
Test run
9.5.1.
Direction of rotation: check
32
6.
If you override the tripping point inadvertently (ratchet click is heard after the
pointer has snapped): Continue turning the setting spindle in the same direction
and repeat setting process.
Perform test run only once all settings previously described have been performed.
Valve damage due to incorrect direction of rotation!
If the direction of rotation is wrong, switch off immediately (press STOP).
Eliminate cause, i.e. correct phase sequence for cable set wall bracket.
Repeat test run.
1.
Move actuator manually to intermediate position or to sufficient distance from
end position.
2.
Set selector switch to position Local control (LOCAL).
3.
Switch on actuator in running direction CLOSE and observe the direction of
rotation:
with indicator disc: step 4
without indicator disc: step 5 (hollow shaft)
Switch off before reaching the end position.
4.
With indicator disc:
Observe direction of rotation.
The direction of rotation is correct, if actuator runs in direction CLOSE
and indicator disc turns counterclockwise.
SA 07.2
SA 16.2/SAR 07.2
AMB 01.1/AMB02.1
SAR 16.2