Current Values: Adjust - AUMA SA 07.2 Operation Instructions Manual

Multi-turn actuators with actuator controls auma matic basic amb 01.1/amb02.1
Hide thumbs Also See for SA 07.2:
Table of Contents

Advertisement

SA 07.2
SA 16.2/SAR 07.2
AMB 01.1/AMB02.1
Information
Activate setting mode
Set measuring range
9.6.2.

Current values: adjust

Information
SAR 16.2
Both measuring ranges 0/4
be set.
During setting process, the measuring range (normal or inverse operation) is
assigned to the end positions by push button S1/S2 assignment.
Setting mode activating clears the setting in both end positions and sets the
output current to a value of 3.5 mA. After activation, both end values (0/4 mA
and 20 mA) need to be reset.
In case of inadvertent incorrect adjustment, the settings can always be reset
by renewed activation of the setting mode (simultaneous pressing of [S1] and
[S2]).
1.
Press both push buttons [S1] and [S2] and hold down for 5 seconds:
By pulsing double flashes, the LED indicates that the setting mode is correctly
activated:
For any other LED flash sequence (single/triple flashing): Refer to <Faults
during commissioning>.
2.
Operate valve in one of the end positions (OPEN/CLOSED).
3.
Set desired output current (0/4 mA or 20 mA):
for 4 mA: Hold down push button [S1] for approx. 3 seconds,
until LED is slowly blinking
for 0 mA: Hold down push button [S1] for approx. 6 seconds,
until LED is blinking fast
for 20 mA: Hold down push button [S2] for approx. 3 seconds,
until LED is illuminated
4.
Operate valve into opposite end position.
The value set in end position (0/4 mA or 20 mA) does not change during travel
in setting mode.
5.
Perform setting in the second end position following the same steps.
6.
Approach both end positions again to check the setting.
If the measuring range cannot be set:
Refer to <Faults during commissioning>.
If the current values (0/4/20 mA) are incorrect:
Refer to <Current values: adjust>.
If the current value fluctuates (e.g. between 4.0
<LED end position signalling: switch on/off>.
The current values (0/4/20 mA) set in end positions can be adjusted at any time.
Conventional values are e.g. 0.1 mA (instead of 0 mA) or 4.1 mA (instead of 4 mA).
If the current value fluctuates (e.g. between 4.0
signalling> must be switched on for current adjustment.
Commissioning (basic settings)
20 mA and 20
0/4 mA (inverse operation) can
.
.
.
4.2 mA), the <LED end position
4.2 mA):
35