Commissioning
controls settings
Figure 35: Relay board; left: version B02, right: version B04
Table 11: Feedback signals setting
Function
(Signal at terminal XK ...
Torque switch tripped in mid-travel and/or
Thermoswitch or thermal overload relay tripped
No torque switch tripped in mid-travel
No thermoswitch or no thermal overload relay tripped
Torque switch tripped in mid-travel
No torque switch tripped in mid-travel
No function
Torque switch tripped in mid-travel
No torque switch tripped in mid-travel
No thermoswitch or no thermal overload relay tripped
Torque switch tripped in mid-travel
No torque switch tripped in mid-travel
Thermoswitch or thermal overload relay tripped
Torque switch tripped in mid-travel
No torque switch tripped in mid-travel
No function
Common connection
1)
refer to order-related wiring diagram BSP ...
10.7.
EMERGENCY command (EMERGENCY - OPEN/EMERGENCY - CLOSE): set
EMERGENCY behaviour
Connection
44
1)
active, if function matches)
— (Option) —
In case an EMERGENCY command is issued, the actuator will run to the defined
end position:
For setting EMERGENCY - CLOSE: Actuator runs to end position CLOSED.
For setting EMERGENCY - OPEN: Actuator runs to end position OPEN.
The EMERGENCY command is effective for all three selector switch positions
(LOCAL, OFF, REMOTE).
The EMERGENCY command is initiated by a signal at the
(refer to wiring diagram).
The
ESD COMMAND
(quiescent current principle). If an EMERGENCY command is issued (signal is
cancelled = NO contact activated), the actuator runs to the defined end position.
SA 07.2
input must be connected via an NC contact to the control voltage
SA 16.2/SAR 07.2
SAR 16.2
AMB 01.1/AMB02.1
Signal at termin-
Link
al
XK 16
XK 15
XK 13
XK 16
XK 15
XK 13
XK 16
XK 15
XK 13
XK 16
XK 15
XK 13
XK 16
XK 15
XK 13
XK 14
ESD COMMAND
input