B600 Retrofit Zonex Module; D8125 Expansion - Bosch B9512G Installation And System Reference Manual

Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

80
en | Off-board points
Callout ᅳ Description
1 ᅳ B299 POPEX Module
2 ᅳ POPIT device
3 ᅳPOPIT address switches
4 ᅳ POPIT sensor loop
5 ᅳ33 kΩ EOL resistor (P/N: 15-03130-022)
13.3

B600 Retrofit ZONEX Module

The B600 Retrofit (ZONEX) module enables the use of ZONEX devices on the B9512G/B8512G
control panel. The B600 module connects to the control panel through a proprietary
connection (cable provided with module).
The control panel supports one B600 module.
13.3.1

D8125 expansion

The control panel supports up to two of the following modules (referred throughout this
section as "D8125") through the use of the B600:
Ensure that there is enough power for the module and other powered devices you want
connected to the system.
Refer to On-board outputs, page 66.
Caution!
Remove all power (AC and battery) before making any connections. Failure to do so might
!
result in personal injury and/or equipment damage.
The B9512G using a D8125 can use point of protection input transponder (POPIT) modules to
provide a maximum of 238 off-board points. The B8512G using a D8125 provides up to 91 off-
board points.
D9127 POPITs use the D8125 POPEX Module to report to the control panel. Each D8125
supports up to 119 POPIT points. Connect two D8125 modules to the B9512G to bring the
total number of POPIT points to 238.
The control panel annunciates activity only for each POPIT, not for each detection device
connected to the sensor loop.
D9127 Module enclosures are made of UL Listed fire resistant material. D9127T Modules
contain tamper switches, while D9127U Modules do not. UL requires D9127T Modules for
certificated installations.
Notice!
The expansion loop can be shared between fire and non-fire devices where the POPIT module
provides data isolation between the input and the expansion loop connections.
2016.06 | 08 | F.01U.303.996
D8125 Zone Expansion Module
D8125MUX Multiplex Bus Interface
D8125INV Wireless Interface Module
D8125CW-V2 Commercial Wireless Interface Module
Points 9 to 127 connect to the first D8125.
Points 129 to 247 connect to the second D8125.
Installation and System Reference Guide
Control Panels
Bosch Security Systems, Inc.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

B9512g-eB8512g-eB8512g

Table of Contents