Specifications - Bosch B9512G Installation And System Reference Manual

Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

164 en | Specifications
21

Specifications

Control panel power supply specifications
Voltage input
Primary
(power supply)
Secondary
Current
Control Panel: Idle 190 mA; Alarm 265 mA
requirements
Refer to the Current Rating Chart for Standby Battery Calculations section in the Control Panels
(B9512G/B8512G) Installation and System Reference Guide (this document) for the current
draw requirements of other system components.
2
Power outputs
All external connections are power-limited except battery terminals.
Continuous
Power
Outputs
Alarm Power
Output
Switched
Aux Power
Fire and
Fire/
Burglary
Systems
1
Requires a UL Listed power supply.
2
For UL 864 applications, refer to US1B LIt differences compatible devices.
Minimum
10.2 VDC
operating
voltage
SDI bus
SDI bus A:
SDI bus B:
SDI2 bus
SDI2 bus A:
SDI2 bus B:
Network
Built-in 10/100 Ethernet LAN (RJ-45 connector)
2016.06 | 08 | F.01U.303.996
Terminals
16.5 VAC 40 VA class 2 plug-in transformer (D1640)
1
and 2
Terminals
Use 12 VDC sealed lead-acid rechargeable battery (7 Ah, 18 Ah, or
4
38 Ah). The control panel supports up to 38 Ah of battery. If you
and 5
use two batteries, they must have the same capacity and you must
connect them using the D122/D122L Dual Battery Harness.
1.4 A maximum at 12.0 VDC nominal (continuous supply) total for all devices
and outputs including the ZONEX connection, the plug-in module connector,
and Terminals 3, 26, and 30.
2.0 A maximum (1.4 A max for commercial fire) at 12.0 VDC nominal output for
all devices and outputs including the ZONEX connection, the plug-in module
connector, and Terminals 3, 6, 7, 26, and 30. Output can be steady or one of
three pulsed patterns depending on programming. Refer to Relays in the
Online Help for RPS.
Terminal
1.4 A maximum at 12.0 VDC nominal output. Continuous output is
8
interrupted by Sensor Reset or alarm verification depending on
programming. Refer to Relays in RPS Help or the Control Panels
(B9512G/B8512G) Program Entry Guide.
To comply with UL 985 and 864 listing standards for fire alarm systems
(effective March 1, 1989), the total combined continuous and alarm current
draw for the system during alarm conditions must be limited to 1.4 A provided
by the primary power supply (rectified AC). If current draw for the system
exceeds 1.4 A, remove connected devices until the current draw falls below
1.4 A. Then, connect the removed devices to an external power supply
as B520).
9 VDC 4572 m (15000 ft) maximum
9 VDC 4572 m (15000 ft) maximum
12 VDC nominal (7500 ft) maximum
12 VDC nominal (7500 ft) maximum
Installation and System Reference Guide
2
2
Control Panels
1
(such
Bosch Security Systems, Inc.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

B9512g-eB8512g-eB8512g

Table of Contents