Telephone Communications; B430 Plug-In Telephone Communicator; Supervision; Installation And Module Wiring (B430) - Bosch B9512G Installation And System Reference Manual

Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

44
en | Telephone communications
7

Telephone communications

The control panel supports telephone communications through the B430 Plug-in Telephone
Communicator.
7.1

B430 Plug-in Telephone Communicator

The B430 Plug-in Telephone Communicator provides communication over PSTN. The module
provides a single telephone interface RJ-45 connector for connecting the phone line. The
module plugs directly into the control panel with no additional connections required.
The control panel supports two plug-in modules plugged directly into the control panel board.
This section includes basic installation instructions. For detailed installation instructions, refer
to the Plug-in Telephone Communicator (B430) Installation Guide.
Notification
The B430 module by Bosch Security Systems, Inc. is registered with the Federal
Communication Commission (FCC) under Part 68, for connection to the public telephone
system using an RJ31X or RJ38X phone line connection jack installed by the local telephone
company.
Do not connect registered equipment to party lines or coin-operated telephones. Notify the
local telephone company and provide the following information before connecting the control
panel to the telephone network:
7.1.1

Supervision

The control panel supervises the phone line. You can configure the supervision time using
RPS.
7.1.2

Installation and module wiring (B430)

Ensure that there is enough power for the module and other powered devices you want
connected to the system.
Refer to On-board outputs, page 66.
Caution!
Remove all power (AC and battery) before making any connections. Failure to do so might
!
result in personal injury and/or equipment damage.
Install the module
The module plugs into a connector and is held in place with a plug-in module retention clip.
The module handle and support on top of the module hold the unit during installation.
Plug the module into a control panel by aligning the module with the control panel's on-board
connector. The retention clip has a locking device to help hold the card in position. Pull the
locking device back. Align the PCB metal contacts with the on-board connector. Push the
module into place. The retention clip snaps closed and secures the module in place.
Wire to the phone line
The module has pads on both sides of the board to connect a test telephone set. Connect one
end of a D162 or D161 Modular Telephone Cord to the phone line, and connect the other end
to a RJ31X or RJ38X phone jack to make proper connection to the phone line.
2016.06 | 08 | F.01U.303.996
The particular line to which you connect the module
Make (Bosch Security Systems, Inc.), model (B9512G/B8512G), and serial number of the
control panel
FCC registration number: ESVAL00BB430
Ringer eq: 0.0B