Local Rps Programming; Installation And Control Panel Wiring (B426) - Bosch B9512G Installation And System Reference Manual

Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

Control Panels
If a B426 fails all communication with the DNS, a system fault indicating Network Module #
Address Error shows on all keypads and the control panel sends a trouble event to the central
stations, if enabled.
8.3.4

Local RPS programming

Use the B426 IP Direct connect feature to locally connect with RPS. This connection method
requires a direct IP connection from the RPS computer to theB426 Ethernet port.
Connecting the B426 to RPS using IP Direct:
1.
2.
3.
4.
For more information on using AutoIP, refer to AutoIP, page 184.
8.3.5

Installation and control panel wiring (B426)

Ensure that there is enough power for the module and other powered devices you want
connected to the system.
Refer to On-board outputs, page 66.
Caution!
Remove all power (AC and battery) before making any connections. Failure to do so might
!
result in personal injury and/or equipment damage.
Install the module
1.
2.
3.
Wire the module
When you wire an SDI2 module to a control panel, you can use either the terminal strip
labeled with PWR, A, B, and COM to wire to corresponding terminals labeled 27 through 30
(or 23 through 26 if configured for SDI2) on the control panel, or you can use the interconnect
wiring connector and the included interconnect cable.
For terminal wiring, use 18 AWG to 22 AWG (1.02 mm to 0.65 mm) wire.
Notice!
Use either the terminal strip wiring or interconnect wiring to the control panel. Do not use
both. When connecting multiple modules, you can combine terminal strip and interconnect
wiring connectors in series.
The module has an Ethernet RJ-45 port for connection to an Ethernet network. Connect an
Ethernet cable between the Ethernet jack on the module and a network jack.
Bosch Security Systems, Inc.
If the B426 does not use the Ethernet for IP communication, perform Steps 2 and 3. If the
B426 does use the Ethernet for IP communication, power down the B426 and remove the
Ethernet cable that connects it to the network.
Connect the B426 to the RPS computer using the Ethernet ports and a standard Ethernet
cable, and apply power to the B426, if applicable. Within 2 minutes, the RPS computer
assigns an IP address using AutoIP.
In RPS, open the control panel account and click the Connect button. From the Connect
Via drop-down list select IP Direct. Click Connect. Once connected, perform the
necessary tasks, and disconnect when finished.
Reconnect the cable used for IP communication, if applicable.
Set the module address to one using the address switch before you install it in the
enclosure.
Install the module in the enclosure with the control panel or in an adjacent enclosure that
is no more than 1000 ft (305 m) using 18 AWG to 22 AWG (1.02 mm to 0.65 mm) wire
from the control panel.
Use the screws provided with the module to secure the module in the enclosure.
Installation and System Reference Guide
IP communications | en
53