Dual Eol Resistor Circuit Style - Bosch B9512G Installation And System Reference Manual

Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

Control Panels
2
3
2
3
2
Figure 12.13: On-board point sensor loop wiring, single EOL resistor
Callout ᅳ Description
1 ᅳ 100 Ω maximum
2 ᅳ Point input terminal
3 ᅳ Common
4 ᅳ Normally closed contacts (NC)
5 ᅳ Normally open contacts (NO)
6 ᅳ Combination: Normally open contacts and normally closed contacts (NO/NC)
7 ᅳ 1 kΩ EOL resistor (ICP-1K22AWG-10)
8 ᅳ Brown
9 ᅳ Black
10 ᅳ Red
Point voltage parameters
Point voltage parameters are specified. Refer to Specifications, page 164.
12.1.2

Dual EOL resistor circuit style

Notice!
For the dual EOL resistor circuit style order ICP-1K22AWG-10, package of 10 1.0 kΩ EOL
resistors.
Point
COM
Figure 12.14: Input wiring with dual EOL resistors
Callout - Description
1 - Point sensor loop terminals
Bosch Security Systems, Inc.
2
1
NC
3
Installation and System Reference Guide
1
4
5
6
4
On-board points | en
73
7
1 kW
8
9
10
2016.06 | 08 | F.01U.303.996