Other Control
5. Other Control
5.1
Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using "Demand 1 Setting" or "Demand 2 Setting".
To operate the unit with this mode, additional setting of "Continuous Demand Setting" or
external input by external control adaptor is required.
Demand 1
Demand 2
5.2
Heating Operation Prohibition
Heating operation is prohibited above 24°C ambient temperature.
52
Set item
Condition
Mode 1
Mode 2
Mode 3
Content
The compressor operates at approx. 60% or less of rating.
The compressor operates at approx. 70% or less of rating.
The compressor operates at approx. 80% or less of rating.
The compressor operates at approx. 40% or less of rating.
SiBE28-805
Function