" Outdoor Unit: Malfunction of Inverter Radiating Fin
Temperature Rise
L4
Remote
Controller
Display
Applicable
CMSQ200A7, 250A7
Models
Method of
Fin temperature is detected by the thermistor of the radiation fin.
Malfunction
Detection
Malfunction
When the temperature of the inverter radiation fin increases above 93°C.
Decision
Conditions
Supposed
Causes
Troubleshooting
Power OFF
Power ON
Troubleshooting
Actuation of fin thermal (Actuates above 93°C)
Defect of inverter PC board
Defect of fin thermistor
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Fin temperature
of the compressor
inverter is high.
Remove and insert the fin
thermistor connector "X111A".
Turn ON
the power supply,
and then check whether or
not the malfunction
recurs.
Troubleshooting by Indication on the Remote Controller
YES
If the fin reaches a
temperature of 93˚C, the
malfunction will occur.
NO
YES
NO
Faulty radiation from the
switch box:
Conduct the checks
shown below.
• Radiation fin for stains
• Airflow for interference
• Fan propeller for damage
• Whether or not outdoor
temperature is too high
Replace the inverter
PC board.
End of measures
• It is supposed that
radiation fin
temperature has risen
due to on-site causes.
Conduct the checks
shown below.
• Radiation fin for stains
• Airflow for interference
• Fan propeller for
damage
• Whether or not
outdoor temperature
is too high
175