Uc" Address Duplication Of Centralized Controller - Daikin CMSQ200A7W1B Service Manual

Hide thumbs Also See for CMSQ200A7W1B:
Table of Contents

Advertisement

SiBE28-805
UC
3.48 "
" Address Duplication of Centralized Controller
UC
Remote
Controller
Display
Applicable
All models of indoor unit
Centralized controller
Models
Method of
The principal indoor unit detects the same address as that of its own on any other indoor unit.
Malfunction
Detection
Malfunction
The malfunction decision is made as soon as the abnormality aforementioned is detected.
Decision
Conditions
Supposed
Causes
Troubleshooting
Troubleshooting
Address duplication of centralized controller
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
The centralized address is
duplicated.
Troubleshooting by Indication on the Remote Controller
Make setting change so that
the centralized address will
not be duplicated.