(2) The heater control (ON/OFF)
[Fan residual operation]
While the heater turns OFF, in order to prevent the activation of the thermal protector, the fan
conducts residual operation for a given period of time after the heater turns OFF. (This
operation is conducted regardless of with or without heater equipped.)
Residual operation time = 100 seconds on ceiling suspended type or 60 seconds on other types

6.10 List of Swing Flap Operations

Swing flaps operate as shown in table below.
Hot start from defrosting
operation
Defrosting operation
Heating
Thermostat OFF
Hot start from thermostat
OFF mode (for prevention
of cold air)
Stop
Thermostat ON in dry
operation using micro
computer
Thermostat OFF in dry
operation using micro
computer
Thermostat OFF in
Cooling
cooling
Stop
Micro computer control
(including cooling
operation)
Function
is conducted by converting
the heater temperature into
the condensing pressure
equivalent saturated
temperature (Tc) according
to the temperature detection
through the high pressure sensor (SINPH) of the outdoor unit.
Swing
Wind direction set OFF
Swing
Wind direction set OFF
Swing
Wind direction set LL
Swing
Wind direction set LL
Swing
Wind direction set OFF
Swing
Wind direction set L*
Swing
Wind direction set
Swing
Wind direction set Set
Swing
Wind direction set OFF
Swing
Wind direction set L
ON
50ºC
Fan
OFF
OFF
LL
LL
OFF
1
L*
1
OFF or L
Set
OFF
L
Outline of Control (Indoor Unit)
Condensing pressure
60ºC
equivalent saturated
temperature
OFF
Flap
FMCQ
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
Swing
Set
Swing
Horizontal or Set
Swing
Set
Horizontal
Horizontal
Swing
Set
*1. L or LL only on FMCQ models