Daikin CMSQ200A7W1B Service Manual page 99

Hide thumbs Also See for CMSQ200A7W1B:
Table of Contents

Advertisement

Field Setting
(6) External ON/OFF Input
This input is used for "ON / OFF operation" and "Protection device input" from the outside. The
input is performed from the T1-T1 terminal of the operation terminal block (X1A) in the electric
component box.
Setting Table
(7) Thermostat Switching
Differential value during thermostat ON/OFF control can be changed. (For details, refer to "6.4
Thermostat Control while in Normal Operation" on page 58.)
(8) Airflow Setting when Heating Thermostat is OFF
This setting is used to set airflow when heating thermostat is OFF.
(9) Setting of Operation Mode to "AUTO"
This setting makes it possible to change differential values for mode selection while in automatic
operation mode.
The automatic operation mode setting is made by the use of the "Operation Mode Selector"
button.
88
Setting
Mode No.
Switch No.
12 (22)
1
Mode No.
12(22)
When thermostat OFF airflow volume up mode is used, careful consideration is required
before deciding installation location. During heating operation, this setting takes precedence
over "Fan Stop When Thermostat is OFF."
Mode No.
12 (22)
Mode No.
Setting switch No.
12 (22)
4
F2 T1 T2
Forced stop
Input A
Setting
Operation by input of the signal A
Position No.
ON: Forced stop (prohibition of using the remote
01
controller)
OFF: Permission of using the remote controller
OFF → ON: Permission of operation
02
ON → OFF: Stop
ON: Operation
03
OFF: The system stops, then the applicable unit
indicates "A0". The other indoor units indicate "U9".
First Code No.
Second Code No.
2
First Code No.
Second Code No.
3
01
02
0°C
1°C
2°C
Differential value
01
02
01
02
Preset airflow
Setting position No.
03
04
05
06
3°C
4°C
5°C
SiBE28-805
1ºC
0.5ºC
Contents
LL airflow
07
08
6°C
7°C
Test Operation

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fmdq50-125a7v3bCmsq250a7w1bFmcq50-125a7veb

Table of Contents