Daikin CMSQ200A7W1B Service Manual page 108

Hide thumbs Also See for CMSQ200A7W1B:
Table of Contents

Advertisement

SiBE28-805
Setting item
Indoor unit fan
1
forced H operation
Indoor unit forced
2
operation
Change of targeted
evaporating
3
temperature
(in cooling)
Change of targeted
condensing
4
temperature
(in heating)
Setting of defrost
5
selection
Setting of
6
sequential startup
Emergency
7
operation (*1)
Additional
8
refrigerant
charging (*1)
Refrigerant
9
recovery mode (*1)
Vacuuming mode
10
(*1)
ENECUT test
11
operation
Power transistor
12
check mode
Setting of model
13
with spare PC
board
For setting items of (*1), refer to detailed information provided on page 108 onward.
Test Operation
Content and objective of setting
Used to operate the indoor unit in the
stopped state in forced H operation mode.
Used to operate the indoor unit in forced
operation mode.
In cooling operation, used to change the
targeted evaporating temperature for
compressor capacity control.
In heating operation, used to change the
targeted condensing temperature for
compressor capacity control.
Used to change a temperature at which the
defrost operation is initiated, thus making
the initiation easy or hard.
Used to start units not in sequence but
simultaneously.
If the compressor has a failure, used to
prohibit the operation of compressor(s)
concerned or outdoor unit(s) concerned
and to conduct emergency operation of the
system only with operable compressor(s)
or outdoor unit(s).
If a necessary amount of refrigerant cannot
be charged due to the stop of outdoor unit,
operate the outdoor unit and then refill
refrigerant.
Used to recover refrigerant on site.
With operations of indoor and outdoor units
prohibited, fully open the expansion valve
of the indoor and outdoor units.
Used to conduct vacuuming on site.
Fully open the expansion valves of the
indoor and outdoor units, and energize part
of solenoid valves. Use a vacuum pump to
conduct vacuuming.
Used to forcedly turn ON the ENECUT.
(Be noted this mode is not functional with
the indoor unit remote controller turned
ON.)
Used for the troubleshooting of DC
compressors.
Inverter waveform output makes it possible
to judge whether a malfunction results from
the compressor or the PC board.
In order to replace the PC board by a spare
one, be sure to make model setting.
Overview of setting procedure
Set No. 5 of "Setting mode 2" to indoor unit
forced fan H.
Set No. 6 of "Setting mode 2" to indoor unit
forced operation mode.
Select high side or low side with No. 8 of
"Setting mode 2".
Select high side or low side with No. 9 of
"Setting mode 2".
Select fast side or slow side with No. 10 of
"Setting mode 2".
Set No. 11 of "Setting mode 2" to NONE.
Make this setting while in "Setting mode 2".
For system with a single outdoor unit: Set
with No. 19 or 42.
For system with multiple outdoor units: Set
with No. 38, 39, or 40.
Set No. 20 of "Setting mode 2" to ON and
then charge refrigerant.
Set No. 21 of "Setting mode 2" to ON.
Set No. 21 of "Setting mode 2" to ON.
Set No. 24 of "Setting mode 2" to ON.
Set No. 28 of "Setting mode 2" to ON.
For this setting, set the DS2-2, -3, and-4
switches on the PC board to the model
concerned.
Field Setting