Daikin CMSQ200A7W1B Service Manual page 52

Hide thumbs Also See for CMSQ200A7W1B:
Table of Contents

Advertisement

SiBE28-805
3.2.2 Oil Return Operation in Heating Operation
Outdoor Unit Actuator
Compressor
Outdoor unit fan
Four way valve
Main motorized valve (EV1)
Subcooling motorized valve (EV2)
Hot gas bypass valve (SVP)
Accumulator oil return valve (SVO)
Injection (SVT) (CMSQ200A7 model only)
Ending conditions
Fan
Electronic expansion valve
Function
Oil return preparation
operation
Upper limit control
STEP7
or
STEP8
ON
SH control → 480 pls
SH control
OFF
ON
OFF
170 sec.
Indoor unit actuator
Thermostat ON unit
Stopping unit
Thermostat OFF unit
Thermostat ON unit
Stopping unit
Thermostat OFF unit
Oil return operation
176 Hz
OFF
OFF
480 pls
0 pls
OFF
ON
OFF
• 4 min.
or
• Ts - Te<5°C
Heating oil return operation
Oil return EV opening degree
Oil return EV opening degree
Special Control
Post-oil-return operation
124 Hz
2-steps increase/20sec.
till Pc - Pe>0.4 MPa
STEP8
ON
55 pls
0 pls
OFF
ON
OFF
• 10 sec.
or
• Pc - Pe>0.4MPa
OFF
OFF
OFF
256 pls
41