SiBE28-805
4.5
Injection Control (only for CMSQ200A7)
For transitional rise in discharge pipe temperature, have the liquid refrigerant flow into the
suction side to reduce the discharge pipe temperature for the compressor protection.
HTdi > 112˚C
Function
SVT = OFF
HTdi < 107˚C
SVT = ON
HTdi: Correction value of the discharge pipe
temperature on the INV compressor.
Protection Control
51