7.2.2 To open the switch box cover of the indoor unit ..22 7.12.4 Appliance categories and pipe lengths ......40 Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
............... 78 Indicates a situation that could result in electrocution. 13.3.3 Symptom: The system is making gurgling noises after commissioning ............ 78 CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Indoor part (Hybrid module + gas Total weight: 66 kg module) ▪ Make sure the area is well ventilated. Do NOT block any ventilation openings. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
▪ Open refrigerant cylinders slowly. ▪ Charge the refrigerant in liquid form. Adding it in gas form may prevent normal operation. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Running the product in reversed phase can break the compressor and other parts. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
▪ Current Gas Safety (Installation and Use) Regulations EHYKOMB33AA*: G.C.N. 47-464-01 ▪ All current building regulations The product (hybrid system) is composed of two modules: CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Technical engineering data ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). ▪ The full set of latest technical data is available on the Daikin extranet (authentication required). Installer reference guide at a...
Gas boiler 4.3.1 To unpack the gas boiler Before unpacking, move the gas boiler as close as possible to its installation position. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
To remove the accessories from the gas boiler 1 Remove the accessories. Model identification Example: C HY HBH 05 AA V3 Code Description Residential multi compatible model Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
The digital I/O PCB is required to provide the following signals: Heat output (space heating) (kW) ▪ Alarm output Nominal power (kW) CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
CANNOT be used in systems using propane (G31). Use the connection kit to connect the domestic hot water tank to the indoor unit. Other options Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
(minimum 500 mm, and in case of a valve mounting kit: 800 mm). Distance measured from the floor to the flare nut of the refrigerant piping. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 16
Minimum venting opening area for natural ventilation: indoor unit" on page 93 to calculate the needed values to make sure that your appliance is installed correctly. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Check that the total water volume in the installation is minimum 13.5 litre, the internal water volume of the indoor unit NOT included. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
See the recommended procedure as described in "10.4 Checklist Also read the precautions and requirements in the during commissioning" on page 70. "General safety precautions" chapter. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Cable section 0.75 mm² till 1.25 mm²; maximum length: 500 m. Applicable for both single user interface and dual user interface connection. Cable section 1.5 mm ; maximum length: 50 m. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
2 Remove the upper and lower screw on the side panel of the switch box. 3 The right panel of the switch box will open. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Installing the indoor unit. 4 Tilt the top of the unit against the wall at the position of the wall bracket. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
2 Fill the condensate trap with water. 3 Slide the condensate trap as far as possible upwards onto the condensate drain connector below the gas boiler. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
A suitable permanent connection to the foul waste pipe should be used. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
When you need to charge additional refrigerant it is recommended to open the refrigerant stop valve after charging. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Service port and service port cap Valve stem Cut exactly at right angles. Field piping connection Remove burrs. Stem cap CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
▪ After handling the service port, tighten the service port cap, and refrigerant piping is wrapped with finishing tape. check for refrigerant leaks. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
The outdoor unit is factory charged with refrigerant, but in some cases the following might be necessary: CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
(GWP) value is 675. Do NOT vent these gases into the atmosphere. ▪ When charging refrigerant, always use protective gloves and safety glasses. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Connecting the water piping of the gas boiler. If necessary, performing a wiring error check. See "10.4.1 To perform a wiring error check" on page 70. Water inlet CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
In case of a tapping demand, it is possible that a small volume of water tapping (<0.3 l) has a temperature higher than 60°C. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Curled single-core wire least 20 mm to prevent condensation on the surface of the b Screw insulation. c Flat washer CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
7.10.5 To connect the main power supply of the indoor unit 1 Connect the main power supply. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
For installation in damp rooms, a fixed connection is obligatory. When working on the electrical circuit ALWAYS isolate the electric supply. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
(for control close to the indoor unit) + 1 user interface 1× in the room (used as room thermostat). 4C From the top 4D From the top centre 1× 1× Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
7.10.12 To connect the space heating ON/OFF output 1 Connect the space heating ON/OFF output cable to the appropriate terminals as shown in the illustration below. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
The concentric adapter piece is equipped with a measuring point for the gas exhaust and one for the air intake. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Following installation methods are supported by the manufacturer. Single boiler installation INFORMATION All piping lengths in the tables below are maximum equivalent piping lengths. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 41
Number of Concentric Dual pipe units Air intake Air intake exhaust exhaust CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Above roof level (to base terminal) From an adjacent wall to flue From an adjacent opening window 1000 Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
(excluding the initial boiler connection). CAUTION Read the installation manuals of the field supplied parts. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
See the outdoor unit installation manual. 7.14 Finishing the indoor unit installation 7.14.1 To close the indoor unit 1 Close the switch box. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
DX cannot be guaranteed over the complete operation range. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 46
To modify an overview setting Example: Modify [1‑01] from 15 to 20. 1 Go to [A.8]: > Installer settings > Overview settings. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 47
When confirmation is complete, the screen will shortly turn OFF and "busy" will be displayed for several seconds. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
The other user interface is automatically set to At unit ▪ a: Add LWT zone ▪ b: Main LWT zone Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 49
Recirculation thermistor (EKTH2) (field supply) ▪ 6 (Type 7) Third-party tank. Water supply Non-return valve (field supply) Range: 0~6. In case of [E‑06]=1 CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 50
(gas or electricity) based on energy prices, resulting in a minimisation of Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 51
[9‑01]°C~min(45, [9‑00])°C (default: 35°C). Note: This value should be lower than [1-02] as for high outdoor temperatures less warm water is required. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 52
▪ For CHYHBH08: 15 l/min (default) The default values have been set to optimise comfort and performance. Take care when changing them. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
(in heating). ▪ comfort (denotes the desired leaving water temperature which results in the highest energy consumption). Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 55
It is recommended NOT to change the room temperature hysteresis as it is set for an optimal use of the system. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 56
([2‑05]), the unit will supply leaving water to the heat emitters to heat up the room again. Code Description [2-06] Room frost protection ▪ 0: disabled (default) ▪ 1: enabled Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 57
[6‑0C] or the weather dependent setpoint, minus the reheat hysteresis. If the tank temperature drops below this value, the tank is heated up. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 59
[5‑00] is set to 1. water temperature drops 5°C below the disinfection target Range –15°C~35°C (default: 5°C) temperature within the duration time. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 60
(see installation). Code Description [A.6.5] [2‑0B] –5°C~5°C, step: 0.5°C (default: 0°C) b (l/min) External static pressure Water flow rate Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Produced energy Flow Consumed gas [7.7] Set weather dependent Main [7.7.1] Main Additional Set weather-dependent heating [7.7.2] Additional Set weather-dependent heating CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
INFORMATION External kWh meter settings are shown but are NOT applicable for this unit. Settings shall NOT be used or changed. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Parameters on the gas boiler Parameter Setting Range Default Description settings Service code — — To access the installer settings, enter the service code (=15) CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 64
Step modulation ▪ 0=OFF during space heating operation ▪ 1=ON during space heating operation It is recommended not to modify this setting. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 65
It is strongly recommended NOT to modify this 22.0 setting. 19.0 15.9 CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 66
3 Remove the front panel from the gas boiler. 4 Remove the sampling point (a) and insert a suitable flue gas analyser probe. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 67
High setting. percentage at maximum power, contact your local dealer. 6 Press simultaneously to exit the test program. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
15 seconds. If after 4 ignition attempts the burner is NOT yet burning, the boiler will go into fault mode. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Burning of the compressor Setting . is correctly set on the gas boiler. The setting might result. must be 0. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Performing an automatic air purge If the water temperature in the system is ≤25°C, the plate heat exchanger will freeze and damage occurs. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Result: SHC or Tank 9 Set the desired position of the bypass valve. Use the buttons to scroll to Bypass. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
X2M/30 and X2M/31. See Action step 2 "7.10.5 To connect the main power supply of the indoor unit" on page 34. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
▪ Installer settings > Commissioning > UFH screed 10 minutes. To perform a test run, switch off the system with the dryout. user interface. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
▪ The water flow coming from the relief valve is high enough, no blockage of the valve or in between piping is suspected. DANGER: RISK OF ELECTROCUTION Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
8 Pull the bottom of the pipe forwards and remove the pipe downwards by turning the pipe alternately clockwise and counterclockwise. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
2 Clean the underside of the heat exchanger. 3 Clean the condensate drain pan with water. 4 Clean the condensate trap with water. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections or defective wiring. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
In an automatic air purge" on some cases, it is normal that the page 71). unit decides to use a low water flow. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Program the start-up of the interrupted by domestic hot water disinfection function when the tapping coming 4 hours NO domestic hot water tapping is expected. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Burner does NOT ignite. "13.3.12 Symptom: The Fan dirty. Clean the fan. burner does NOT ignite" on page 80. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
The indoor unit has an error Check for possible errors on the code. indoor unit. Heat exchanger frozen. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 82
Please contact your dealer. Minimum required flow during heat pump operation 05+08 models 9 l/min Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Following table shows a list of error codes and the possible solutions. Error Cause Possible solution code 10, 11, Sensor fault S1 ▪ Check wiring 12, 13, ▪ Replace S1 CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin extranet (authentication required).
Notes to go through before Notes to go through before starting the unit starting the unit Field wiring terminal for DC CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 86
3-way valve for floor heating/domestic hot water tank Max. load Maximum load Bypass valve for gas boiler Min. load Minimum load Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 87
(7) External room thermostats (7) External room thermostats Only for wireless thermostat Only for wireless thermostat and heat pump convector and heat pump convector CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 88
4 core Heat pump part Gas boiler part 3 core unit power supply: 230 V + earth X2: 2-4-earth Gas boiler 3D107996 Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Gas valve and ignition electrode Main power supply (2=l (BRN), 4=N (BLU)) Power supply fan (230 V) Boiler communication cable Sensor connection CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 91
A value from the table. If A =12.5 m room room consider the value that corresponds to "A =12 m ". room CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
"dm=1.6 kg". ▪ Systems with a total refrigerant charge <1.225 kg are NOT subjected to any requirements to the installation room. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Page 94
0 mm WARNING In case of a different configuration is used, do NOT deviate from requirements mentioned in "6 Preparation" on page 15. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Note: Selecting a flow outside the area of operation can cause damage or malfunction of the unit. Water quality MUST be according to EN directive EC98/83EC. CHYHBH05+08AA + EHYKOMB33A Installer reference guide Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Any modifications to the gas valve MUST be performed by a certified representative of the manufacturer. For more information, contact your dealer. Installer reference guide CHYHBH05+08AA + EHYKOMB33A Daikin hybrid for multi heat pump – heat pump module 4P471761-1A – 2017.10...
Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment NOT made by Daikin that can be combined with product according instructions accompanying documentation.
Field settings table Applicable indoor units CHYHBH05AAV32 CHYHBH08AAV32 Notes 4P471775-1 - 2016.12...
Page 102
Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value User settings └─ Preset values └─ Room temperature 7.4.1.1 Comfort (heating) [3-07]~[3-06], step: A.3.2.4 21°C 7.4.1.2 Eco (heating) [3-07]~[3-06], step: A.3.2.4 19°C └─...
Page 103
Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value A.2.2.B [C-08] External sensor 0: No 1: Outdoor sensor 2: Room sensor A.2.2.C [D-0A] External gas meter 0: Not present 1: 1 /m³...
Page 104
Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value A.6.7 [7-04] 0: Economical 1: Ecological └─ Emergency A.6.C 0: Manual 1: Automatic └─ Overview settings [0-00] Leaving water value for high ambient temp. for LWT add zone heating WD curve. [9-05]~min(45,[9-06])°C, step: 1°C 35°C [0-01]...
Page 105
Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value [5-03] [5-04] [5-05] [5-06] [5-07] [5-08] [5-09] [5-0A] [5-0B] [5-0C] [5-0D] [5-0E] [6-00] The temperature difference determining the heat pump ON temperature. 2~20°C, step: 1°C 2°C [6-01]...
Page 106
Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value [B-04] [C-00] Domestic heating water priority. 0: Solar priority 1: Heat pump priority [C-01] [C-02] [C-03] [C-04] [C-05] What is the thermo request contact type for the main zone? 1: Thermo ON/OFF 2: C/H request [C-06]...