Troubleshooting by Remote Controller

2. Troubleshooting by Remote Controller
2.1

The INSPECTION / TEST Button

The following modes can be selected by using the [Inspection/Test Operation] button on the
remote control.
Indoor unit settings can be made
• Filter sign time
• Airflow direction
• Others
Depress Inspection/Test Operation button
for more than 4 seconds.
Press Inspection/Test Operation
button once.
Following codes can be checked.
• Malfunction codes
• Indoor model code
• Outdoor model code
124
Depress Inspection/Test Operation button
for more than 4 seconds.
Local
setting
mode
Normal
mode
After 10 seconds
Inspection
mode
Press Inspection/Test Operation
button once.
Service data can be obtained.
• Malfunciton code history
Service
• Temperature data of various sections
mode
Service settings can be made.
• Forced fan ON
• Airflow direction/volume setting
Press Inspection/Test Operation button once.
Press Inspection/Test Operation button once.
Or after 30 minutes
Test
operation
Thermostat is forcibly turned on.
mode
SiBE28-805
Troubleshooting

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fmdq50-125a7v3bCmsq250a7w1bFmcq50-125a7veb