Download Print this page

Daikin CMSQ200A7W1B Service Manual: H7" Outdoor Unit: Abnormal Outdoor Fan Motor Signal

Hide thumbs

Advertisement

Troubleshooting by Indication on the Remote Controller
H7
3.21 "
" Outdoor Unit: Abnormal Outdoor Fan Motor Signal
H7
Remote
Controller
Display
Applicable
CMSQ200A7, 250A7
Models
Method of
Detection of abnormal signal from fan motor.
Malfunction
Detection
Malfunction
In case of detection of abnormal signal at starting fan motor.
Decision
Conditions
Supposed
Causes
Troubleshooting
166
Abnormal fan motor signal (circuit malfunction)
Broken, short or disconnection connector of fan motor connection cable
Fan Inverter PC board malfunction
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Turn power off.
Is the fan
motor connector
X2A connected to PC board
for Fan inverter
correctly?
YES
Check of fan motor connector.
( 1)
The
resistance of
fan motor read wire
connector pins between
Vcc-UVW and
GND-UVW
balanced?
YES
1: Disconnect connector (X2A) and measure the following resistance.
3 Orange
1 Yellow
NO
NO
X2A
5 Gray
GND
4 Pink
Vcc
W
2 Blue
V
U
SiBE28-805
Connect correctly.
Replace fan motor.
Replace fan inverter PC Board.
(A3P)
Measure the
resistance
between Vcc-
UVW and
GND-UVW.