Daikin CMSQ200A7W1B Service Manual page 101

Hide thumbs Also See for CMSQ200A7W1B:
Table of Contents

Advertisement

Field Setting
13 (23)
*1 "Mode No." setting is done in a batch for the group. To make or confirm settings for an
*2 The figure of the ceiling height is for the all round outlet. For the settings for four-direction
(13) Airflow Direction Setting
Set the airflow direction of indoor units as given in the table below. (Set when optional air outlet
blocking pad has been installed.) The second code No. is factory set to "01."
Setting Table
(14) Setting of Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
Setting Table
(15) Setting of the Static Pressure Selection
(16) Humidification when Heating Thermostat is OFF
Setting to "Humidification Setting" turns ON the humidifier if suction temperature is 20ºC or
above and turns OFF the humidifier if suction temperature is 18ºC or below when the heating
thermostat is OFF.
90
In the Case of FMCQ100~125 (*
First
Second
Mode
code
code
No.
No.
No.
01
Standard (N)
0
02
High Ceiling (H)
03
Higher Ceiling (S) Lower than 4.5 m Lower than 4.2 m
individual unit, set the internal mode number in parentheses.
(part of corner closed off), three-direction and two-direction outlets, see the installation
manual and technical guide supplied with the separately sold closure material kit.
Mode No.
First Code No.
13 (23)
1
Mode No.
13 (23)
Some indoor unit models are not equipped with draft prevention (upward) function.
Model No.
13 (23)
Mode No.
15 (25)
2
4-Way, 3-Way, 2-Way Outlets)
Setting
4-way Outlets
Lower than 3.4 m Lower than 3.6 m Lower than 4.2 m
Lower than 3.9 m Lower than 4.0 m Lower than 4.2 m
Second Code
No.
01
F : 4-direction airflow
02
T : 3-direction airflow
03
W : 2-direction airflow
First Code No.
Second Code No.
4
First Code No.
Second Code No.
6
First Code No.
Second Code No.
1
Ceiling height
3-way Outlets
2-way Outlets
Setting
Setting
Upward (Draft
01
prevention)
02
Standard
Downward (Ceiling
03
soiling prevention)
External static pressure
01
Standard
02
High static pressure
03
Low static pressure
Setting
01
02
Setting of humidifier
Test Operation
SiBE28-805