A1" Indoor Unit: Pc Board Defect - Daikin CMSQ200A7W1B Service Manual

Hide thumbs Also See for CMSQ200A7W1B:
Table of Contents

Advertisement

SiBE28-805
A1
"
" Indoor Unit: PC Board Defect
3.2
A1
Remote
Controller
Display
Applicable
All indoor unit models
Models
Method of
Check data from E²PROM.
Malfunction
Detection
Malfunction
When data could not be correctly received from the E²PROM
E²PROM : Type of nonvolatile memory. Maintains memory contents even when the power
Decision
supply is turned off.
Conditions
Supposed
Causes
Troubleshooting
Troubleshooting
Defect of indoor unit PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Turn power supply OFF, then
power ON again.
Does
the system return
to normal?
NO
Troubleshooting by Indication on the Remote Controller
YES
The indoor unit PC board is
normal.
External factor other than
malfunction (for example,
noise etc.).
Replace the indoor unit PC
board.