Field Setting
c. Monitor mode
To enter the monitor mode, push the
MODE (BS1) button when in
"Setting mode 1".
<Selection of setting item>
Push the SET (BS2) button and set
the LED display to a setting item.
<Confirmation on setting contents>
Push the RETURN (BS3) button to
display different data of set items.
Push the RETURN (BS3) button and
switches to the initial status of
"Monitor mode".
∗ Push the MODE (BS1) button and
returns to "Setting mode 1".
106
No.
Setting item
0
Various settings
1
C/H unified address
2
Low noise/demand address
3
Not used
4
Airnet address
Number of connected indoor units
5
*1
Number of connected BS units *2
6
Number of connected zone units
7
(Fixed to "0")
8
Number of outdoor units *3
9
Number of BS units *4
Number of BS units *4
10
11
Number of zone units
Contents of malfunction (the
14
latest)
Contents of malfunction
15
(1 cycle before)
Contents of malfunction
16
(2 cycle before)
20
Contents of retry (the latest)
21
Contents of retry (1 cycle before)
22
Contents of retry (2 cycle before)
Number of multi connection
25
outdoor units
The numbers in the "No." column represent the number of times to press the
SET (BS2) button.
*1: Number of connected indoor units
Used to make setting of the number of indoor units connected to an outdoor
unit.
*2: Number of connected BS units
Used to make setting of the number of BS units connected to an outdoor
unit.
*3: Number of outdoor units
Used to make setting of the number of outdoor units connected to DIII-NET
that is one of the communication lines.
*4: Number of BS units
Used to make setting of the number of BS units connected to DIII-NET that is
one of the communication lines.
LED display
H1P
H2P H3P
H4P
H5P H6P
l h h h h h h
l h h h h h k
l h h h h k h
l h h h h k k
l h h h k h h
l h h h k h k
l h h h k k h
l h h h k k k
l h h k h h h
l h h k h h k
l h h k h k h
l h h k h k k
l h h k k k h
l h h k k k k
l h k h h h h
l h k h k h h
l h k h k h k
l h k h k k h
l h k k h h k
SiBE28-805
Data display
H7P
Lower 4 digits
Lower 6 digits
Lower 4 digits:
upper
Lower 4 digits:
lower
Lower 6 digits
Malfunction
code table
Refer page
134.
Lower 6 digits
Test Operation