Uc" Address Duplication Of Centralized Controller - Daikin GQI-Eco Series Service Manual

R-410a 50hz
Table of Contents

Advertisement

Troubleshooting by Remote Controller
UC
4.38 "
" Address Duplication of Centralized Controller
UC
Remote
Controller
Display
All models of indoor unit
Applicable
Centralized controller
Models
The principal indoor unit detects the same address as that of its own on any other indoor unit.
Method of Error
Detection
The error decision is made as soon as the abnormality aforementioned is detected.
Error Decision
Conditions
 Address duplication of centralized controller
Supposed
Causes
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
The centralized address is duplicated.
180
ESIE15-13B
Make setting change so that the
centralized address will not be
duplicated.