L4" Outdoor Unit: Malfunction Of Inverter Radiating Fin Temperature Rise - Daikin ERSQ 011AAV1 Service Manual

Table of Contents

Advertisement

ESIE09-08
3.38 "L4 " Outdoor Unit: Malfunction of Inverter Radiating Fin
Temperature Rise
L4
Remote Control
Display
Applicable
ER*Q 011~016*
Models
Method of
Fin temperature is detected by the thermistor of the radiation fin.
Malfunction
Detection
Malfunction
When the temperature of the inverter radiation fin increases above 83°C.
Decision
Conditions
Supposed
Causes
Troubleshooting
Troubleshooting
Actuation of fin thermal (Actuates above 83°C)
Defect of inverter PC board (A2P)
Defect of fin thermistor
Be sure to turn off power switch before connecting or disconnecting connector,
otherwise parts may be damaged.
Caution
The radiator
fin temperature is
supposed to have risen
to 84 C or more.
NO
Is the
connector X111A of
the fin thermistor properly
connected to the outdoor
PC board?
YES
Turn ON the power supply, and then
press the remote control check
button once.
Does the
malfunction code "L4"
recur when the unit starts
operation?
NO
Troubleshooting by Indication on the Remote Controller
YES
NO
YES
Faulty heat radiation of power unit
Air suction opening blocked
Dirty radiator fin
High outdoor temperature
Check heat conductive paste
Properly connect.
Replace the inverter PC board assy
(A2P)
Continue operation.
177