2.3.59 L4-00 – Outdoor unit: Malfunction of inverter radiating fin temperature rise
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the main PCB. See
Possible cause: Faulty main PCB.
2 Perform a check of the outdoor unit fan motor. See
4
motor" [
 217].
Possible cause: Faulty outdoor unit fan motor.
3 Check if the power supply is conform with the regulations. See
4
circuit" [
 284].
Possible cause:
▪ Faulty or disturbance of the power supply (imbalance >4%),
▪ Power drop,
▪ Short circuit.
4 Clean the outdoor heat exchanger. See "5 Maintenance" [
Possible cause: Dirty outdoor heat exchanger.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Trigger
Radiating fin thermistor
measures a too high
temperature.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the outdoor unit fan motor. See
4
motor" [
 217].
Possible cause: Faulty outdoor unit fan motor.
2 Check if the power supply is conform with the regulations. See
4
circuit" [
 284].
Possible cause:
▪ Faulty or disturbance of the power supply (imbalance >4%),
▪ Power drop,
▪ Short circuit.
3 Perform a check of the main PCB. See
Possible cause: Faulty main PCB.
Prerequisite: Stop the unit operation via the user interface.
4 Turn OFF the respective circuit breaker.
"3.14 Main
Effect
Unit will stop operating.
"3.14 Main
2
Troubleshooting
|
4
PCB" [
 171].
"3.16  Outdoor unit fan
"4.1 Electrical
4
 309].
Reset
Manual reset via user
interface.
"3.16  Outdoor unit fan
"4.1 Electrical
4
PCB" [
 171].
Service manual
51