Power factor
Table 10‑3. DC Electrical specifications
Description
Maximum number of
input strings
Maximum operating
input current
Maximum DC power
Nominal DC voltage
Full power MPPT range
Maximum voltage
Maximum short circuit
current
Startup voltage
Operating voltage range
DC insulation
DC fuses
570-1003552-05A
Factory setting > 0.99
Field adjustable range ±0.8
Specifications for 600 Series
10
AE 3TL-12kW: 2 x 27.5 A
AE 3TL-16kW: 2 x 33.0 A
AE 3TL-20kW: 2 x 37.5 A
AE 3TL-23kW: 2 x 40.0 A
AE 3TL-12kW: 21.0 kW
AE 3TL-16kW: 28.0 kW
AE 3TL-20kW: 35.0 kW
AE 3TL-23kW: 40.6 kW
360 V
AE 3TL-12kW: 225 to 450 V
AE 3TL-16kW: 250 to 450 V
AE 3TL-20kW: 275 to 450 V
AE 3TL-23kW: 300 to 450 V
2 x 500 VDC
2 x 76 A
125 to 480 V
Transformerless design: PV array input cannot connect to ground
600 VDC, 15 A cylindrical
midget photovoltaic fuses (20 A
optional)
Specifications
Advanced Energy® AE 3TL Inverters
Specifications for 1000 Series
6
AE 3TL-12kW: 27.5 A
AE 3TL-16kW: 33.0 A
AE 3TL-20kW: 37.5 A
AE 3TL-23kW: 40.0 A
720 V
AE 3TL-12kW: 450 to 900 V
AE 3TL-16kW: 500 to 900 V
AE 3TL-20kW: 550 to 900 V
AE 3TL-23kW: 600 to 900 V
1000 VDC
76 A
200 V
200 to 960 V
1000 VDC, 15 A cylindrical
midget photovoltaic fuses (20 A
optional).
A‑3