Table 9‑1. Inverter faults (Continued)
Display Screen Text
DEVICE FAULT LT
ETHERNET CONNECTION 1
ETHERNET CONNECTION 2
ETHERNET CONNECTION 3
GEN INSULATION AFILT
GEN INSULATION AFISR
GEN INSULATION LT
GRID FREQUENCY
GRID FREQUENCY FLL
9‑8
Troubleshooting and Solar Energy Technical Support
Operation Condition
Overload shutdown in power
section.
Ethernet connection setup
unsuccessful.
Ethernet disconnected.
There is no 100 Mbit/s
Ethernet connection.
An insulating fault was
detected during the system's
automatic insulation test
(ENS, power section).
An insulating fault was
detected during the system's
automatic insulation test
(ENS, control section).
An insulating fault was
detected during the system's
automatic insulation test
(ENS, power section).
Detection of a utility main
frequency fault (ENS, control
section). This fault indication
is possibly caused by
switching operation on the
utility main.
Detection of a utility main
fault (ENS, control section).
This fault indication is
possibly caused by switching
operation on the utility main.
Description
Acknowledge the fault by
pressing the ESC button
and de-energizeing the
inverter.
Check the Ethernet
connection.
Set up Ethernet
connection with 100 Mbit/
s.
Check the system's
insulation and repair.
1. Inverter will
automatically restart
when utility voltage
and frequency
returns within
normal limits.
2. Contact the grid
operator if the grid
voltage is not in the
normal range.
3. Contact AE Solar
Energy Technical
Support if the grid
voltage is in the
normal range.