8. Lift the inverter using the four side handles and hang it on the wall mount
bracket hooks by aligning the mounting points on the rear of the heatsink.
☞
Important
The lower end of the heatsink should rest against the support on the bottom
front of the wall mount bracket.
Figure 4‑4. Mounting the inverter on the wall mount bracket
9. Fasten the heatsink to the wall mount bracket using two washers and two of the
included screws.
Table 4‑1. Construction anchoring chart
Wall Structure
Concrete masonry unit
(CMU) (full grout or hollow
core)
570-1003552-05A
Due to the weight of the inverter, AE recommends using two people to
lift the inverter and hang it on the wall mount bracket. Follow local or
OSHA guidelines when lifting or moving equipment.
Heatsink cooling fins
Lower edge of heatsink
Fasteners
4 fasteners: 3/8" diameter
expansion anchors
Advanced Energy® AE 3TL Inverters
Embed the four fasteners a
minimum of 6 cm (2.5"). Follow
the manufacturer instructions. All
fasteners must be installed with
fender washers.
Installing
Notes
4‑9