Advanced Energy
SPACING AND CLEARANCES
The inverter requires adequate space for proper cooling. When installed, the inverter
must have the following clearances:
Table 3‑1. Mounting clearances
Location
Top
Bottom
Side
Rear
Front
50 cm (20")
15 cm (6")
Figure 3‑1. Required clearances
☞
Important
If the inverter will be used as the standard disconnect, the inverter must meet
NEC mounting requirements.
When installing the inverter, you should also consider the location of the LEDs and
the display for ease of visibility. AE recommends the display is located
approximately 160 cm (63") above the ground.
3‑2
51 cm (20")
51 cm (20")
15 cm (6"); right side of last inverter is 5 cm (2") clearance
00 cm (0")
Clearance as specified by NEC 110.26.
Planning
Minimum Clearance
15 cm (6")
5 cm (2")