1MRS756014
8.5.
Ethernet Adapter
Modbus/TCP Brigde
Installation and Commissioning Manual
The version information can be read from the device's label. If the device
is updated afterwards, use CET's IP query to get the correct version
information from the device memory. For more information about IP
query, refer to Section 8.3. IP Query.
Obtaining error logs
The following session transfers error.log file through ftp.
C : \ > f t p x . x . x . x
User: abb
Password: abb
f t p > c d l o g
f t p > g e t e r r o r . l o g
f t p > q u i t
SPA-ZC 400
45