Figure 7. Clip and retainer nut locations on exhaust side cabinet rails (example showing
relative positions)
4. Install the shelf (C in Figure 6 on page 20), using these steps:
22
SAN384B-2 Installation, Service, and User Guide
clip nut attachment
for round-hole rails
31
30
29
clip or retainer
nut locations
28
for chassis
27
26
25
clip or retainer
24
nut locations
for shelf
23
a. The shelf can be adjusted to a length of between 27 and 31 inches (68.58
and 78.74 cm) to match the cabinet size. To lengthen or shorten the shelf,
loosen by approximately 1/2 turn the four 6-32 screws in the four slots on
the shelf (I-4 through I-7 Figure 6 on page 20) and adjust the shelf to the
required length.
Note: We recommend two people for the installation of the shelf, one at
either end of the cabinet to support and align it correctly while
attaching it to the cabinet.
b. Tilt the shelf at an angle to fit it between the rails, and then position it
horizontally and level with the shelf mounting tabs on the outside of the
cabinet vertical rails, and aligned with the clip nuts you installed earlier.
c. Secure the shelf to the cabinet with eight 10-32 screws with washers (E in
Figure 6 on page 20), two screws in each corner of the shelf (see Figure 8 on
page 23). Tighten screws according to specifications under "Torque
requirements" on page 21.
Setup for Rails
with Square Holes
31
30
29
28
27
rail
26
25
24
23
retainer nut
(Item G)
Rail