Step
4
5
6
296-1011-202 Rel. 5.0, Doc. Rev. 02.01
Action
Place the lugs of the wires over the posts. Make sure that the lugs for the
black wires are on the posts labeled "RETURN" on the raised brackets, and
that the lugs for the red wires are on the posts labeled "-48V" on the brackets
that are flush with the surface.
Black cable to "RETURN"
D C P
M 2
1
2
3
4
S y s te
5
m
C o n tr
o ll e r
o n ly
6
Tighten nuts to 13 in-lb using the nutdriver.
Secure the cables using a cable tie through the cable mount on the lower right
side of the chassis.
Connecting Power to the Chassis
Red cable to "-48V"
Black cable to "RETURN"
Red cable to "-48V"
D C P
M 1
1
2
3
C on so
le
4
5
6
Chassis Connections
M ai n
Ch as
si s
CVX-0204A
(continued)