CVX 600 Hardware Installation Guide
Chassis Specifications and Clearances
Chassis Specifications and Clearances
Dimensions, Weight, Slot Capacity
The following table lists the dimensions, weight, and slot capacity of the
CVX 600 chassis:
Attribute
Height with AC module
Height without AC module
Width
Depth
Weight: chassis with 6 SMs and AC power
Slots
Clearance
The chassis must have enough clearance around it to ensure proper airflow for
cooling. The following table lists the minimum clearance requirements for the
CVX 600 chassis:
Area
Left side (location of fans)
Right side
Top
Back
Back (for servicing)
A-2
Measurement
10.5 in. (26.7 cm)
7.0 in. (17.8 cm)
17.3 in. (43.94 cm)
16.25 in. (41.3 cm)
70 lb (31.7 kg)
Two for SCCs, combinations of up to 4
DACs and MACs
Minimum Clearance
2.0 in. (5.08 cm)
2.0 in. (5.08 cm)
None
6.0 in. (15.24 cm)
12.0 in. (30.48 cm)
296-1011-202 Rel. 5.0, Doc. Rev. 02.01