Mounting the CVX 600 in a Rack
Properly ventilated
Well lighted

Ceiling Requirements

Consider the following ceiling requirements before you install the rack:
The ceiling should be clear of obstructions such as beams, heating and air
conditioning ducts, water pipes, and lights.
The ceiling should not have sprinklers; however, appropriate fire protection
devices should be available.

Size and Weight Considerations

Before you install the rack at your site, make sure that the equipment room can
accommodate the size and weight of the rack and the CVX 600.
To determine the total weight, add the weight of all of the CVX 600 chassis (about
70 lb, 31.7 kg each for the AC chassis option, NTDZ10BA)
rack.

Reference

For information about general equipment requirements, see the Telcordia Network
Equipment Building Standards (NEBS), General Equipment Requirements
(GR-63).

Nortel Networks PTE 2000 Rack

Nortel Networks offers two types of PTE 2000 racks:
PTE 2000 NEBS-compliant rack (NTRU0134)
PTE 2000 ETSI-compliant rack (NTRU0234)
1-8
Note: The recommended aisle spacing is 29.5 in. (750 mm).