Step
5
6
Using the Compression Terminal
To ground the CVX 600 chassis using the compression terminal, follow these
steps:
Step
1
2
296-1011-202 Rel. 5.0, Doc. Rev. 02.01
Action
Place the grounding connectors over the posts, then secure the connectors
using a 11/32-inch nut driver to tighten the #8 locking nuts to 15 in-lb.
11/32-inch nutdriver
Turn clockwise
to tighten nuts
to 15 in-lb.
Ensure that the other end of the ground cable is properly connected for frame
grounding.
Note: In addition to the grounding location shown in the following
section, the AC chassis option also contains an identical grounding
location in the upper right corner of the rear of the chassis. Either location
may be used.
Action
Locate a suitable ground cable at your facility.
On the back of the chassis, locate the posts with the ground symbol.
Connecting Power to the Chassis
OR
Ground cable
to facility
ground.
CVX-0224A
Chassis Connections
(continued)
2-19