en | Connection
5.1.12

Power

Introduction
The voice alarm controller has the following power connections:
Mains power
Proceed as follows to connect the voice alarm controller to the mains power:
4
Figure 5.16: Voltage selector
Selector
115
230
Table 5.3: Voltage selector
Notice!
The Voice Alarm Controller is delivered with the voltage selector in the 230 V position.
1.
Notice!
The Voice Alarm Controller is delivered with a T6.3L 250 V fuse for a mains voltage of
220 to 240 V(AC).
2.
3.
2013.07 | V2.0 |
Mains power connection.
Back-up power connection.
Select the local mains voltage using the voltage selector on the rear of the voice alarm
controller.
115V~
230V~
Apparatus delivered
Connected for 230V~
Mains voltage V(AC)
100 - 120
220 - 240
Put the correct type of fuse in the voice alarm controller.
Connect a locally approved mains cord to the voice alarm controller.
Connect the mains cord to a locally approved mains outlet.
Installation and Operation manual
Power
Fuse
115 V - 10 AT
230 V - 6,3 AT
Bosch Security Systems B.V.
Plena