Bosch Plena Operating Manual page 147

Table of Contents

Advertisement

Plena
Clause / Requirement
e there shall be provision to switch on
f
g a separate discrete light emitting
7.5 Phased evacuation (option with
requirements)
The VACIE may have a provision to
phase the warning signals to the
emergency loudspeaker zones. The
facility shall be configurable at access
level 3. There may be provision to
switch on and switch off the phased
evacuation sequence by means of a
manual operation at access level 2 (see
Annex A for information on access
levels).
7.6 Silencing of the voice alarm
condition
7.6.1 Silencing of the voice alarm
condition from the CIE
7.6.1.1 Where the voice alarm condition
has been triggered from the CIE, the
VACIE shall respond appropriately to a
silence instruction from the CIE.
Bosch Security Systems B.V.
and switch off delays by means of a
manual operation at access level 2
(see Annex A for information on
access levels);
there may be provision to
automatically switch on and/or
switch off delays by means of a
programmable timer which shall be
configurable at access level 3;
indicator and/or a field on the
alphanumeric display shall be visible
when a fire signal is received and the
delay activated. This indication shall
be suppressed when the VACIE
enters the voice alarm condition.
Installation and Operation manual
Compliance
Plena Voice Alarm System does not
accommodate phased evacuation.
Plena Voice Alarm System is
compliant.
Voice alarm calls triggered from the
CIE can also be stopped from the
CIE. To reset the voice alarm
condition an Acknowledge
Emergency is possible for CIE and
on the front panels of the controller
and remote control panels.
Appendices | en
147
Signature
2013.07 | V2.0 |