Distribute The Alarm Message; Fault State; Acknowledge The Fault State - Bosch Plena Operating Manual

Table of Contents

Advertisement

96
en | Operation
7.4.8

Distribute the alarm message

Distributing the default alarm message is similar to distributing the default alert message (see
section Distribute the alert message, page 94). Push the Alarm message button instead of the
Alert message button. The alarm message can also be distributed by pushing the Alarm
Message button on the fireman's panel.
Figure 7.18: Alarm message button
7.5

Fault State

If a supervised function fails, the system enters the fault state and:
7.5.1

Acknowledge the fault state

The beeper can be switched off by acknowledging the fault state with the Fault Ack button on
the front of the voice alarm controller or the remote controls. The fault state can also be
acknowledged by pushing the Fault Acknowledge button on the fireman's panel.
Figure 7.19: Fault Ack button
The following buttons also acknowledge the fault state and stop the beeper:
2013.07 | V2.0 |
Alert message
Alarm message
EMG mic
Starts a beeper. The beeper is switched off when the fault is acknowledged (see section
Acknowledge the fault state, page 96).
Closes the Fault Status NO output contacts. These status output contact is opened again
when the fault is reset (see section Reset the fault state, page 97).
Lights a fault indicator on the front panels that indicates the source of the fault (see Fault
indicators, page 98). The indicator is switched off when the fault is reset (see section
Reset the fault state, page 97).
Fault
EMG
Ack
Zone select
Reset
Zone1
Alert message button.
Alarm message button.
PTT button of the emergency microphone.
Installation and Operation manual
All call
Indicator test
Zone2
Plena
Bosch Security Systems B.V.