Plena
Clause / Requirement
7.7.2.2 Following a reset operation, the
indication of the correct functional
condition corresponding to any received
signals shall either remain or be re-
established within 20 s.
7.8 Output to fire alarm devices
(option with requirements)
In addition to the voice alarm outputs
the VACIE may have provision for the
automatic transmission of fire alarm
signals to fire alarm devices such as
beacons and vibrating devices. In this
case, the following shall apply:
a it shall be possible to de-activate the
b following de-activation, it shall be
c the fire alarm devices shall not be
d it shall be possible to configure the
7.9 Voice alarm condition output
(option with requirements)
The VACIE may have provision for
transmitting a signal that is in the voice
alarm condition. In this case, it shall
activate the output only in the voice
alarm condition.
Bosch Security Systems B.V.
fire alarm devices at access level 2;
possible to re-activate the fire alarm
devices at access level 2;
de-activated automatically;
VACIE at access level 3 to
automatically reactivate the fire
alarm devices if an alarm is reported
in an other zone.
Installation and Operation manual
Compliance
After a reset operation, the Plena
Voice Alarm System will immediately
indicate the functional condition it is
currently in. It will also immediately
(<<1 s) respond to received signals
that will bring it into another
functional condition.
This option is not supported by the
Plena Voice Alarm System.
Plena Voice Alarm System is
compliant.
The Plena Voice Alarm System
transmits a signal that it is in the
voice alarm condition via the Open
Interface, and via the status contact.
Appendices | en
149
Signature
2013.07 | V2.0 |