en | Appendices
Clause / Requirement
a System availability.
b Power supply availability.
c Any fault condition.
d For systems having numerous
5.3 Automatic fault monitoring
A clear indication shall automatically be
given, at specified locations, e.g. at main
equipment locations, of:
a Short-circuit or disconnection or failure
b Short-circuit or disconnection or failure
c Short-circuit or disconnection or failure
d Rupture of any fuse or operation of
e Failure of microphone, including
2013.07 | V2.0 |
loudspeaker zones, which loudspeaker
zones are selected and the mode of
operation of each zone, i.e. "evacuate"
or "alert" and pre-selection of
emergency microphone. Where different
alarm messages are provided, which are
dependent on the evacuation
requirements, indication of which
message is being broadcast and into
which zone, shall be displayed by a
suitable method. This information shall
be continuously displayed and kept up
to date.
of the primary power source.
of the standby power source.
of any battery charging equipment
associated with the primary or standby
power sources.
circuit breaker, isolator or protective
device that may prevent an emergency
broadcast.
capsule voice coil, pre-amplifier and
essential wiring to the rest of the
system.
Installation and Operation manual
Compliance
Compliant. Indication on
controller, router and call station.
Compliant. Indication on
controller, router and call station.
Compliant. Indication on
controller, router and call station.
Compliant. Indication on
controller, router.The Plena Voice
Alarm System Remote Control is
part of the certified system.If the
Fireman;s Panel is used, there
should only be one emergency
zone, covering all zones of the
system. The Fireman's Panel is an
all call remote control with large
buttons..
Compliant, if properly installed.
Responsibility of the installer.
Backup via 24 V.
Compliant, if properly installed.
Responsibility of the installer.
Backup via 24 V.
Responsibility of the installer.
Supervision of third party
charging equipment is via control
inputs.
Compliant. Fault is indicated on
the controller and router.
Configuration must be set up to
supervise this.
Compliant. Fault is indicated on
the controller and router.
Configuration must be set up to
supervise this.
Plena
Signature
Bosch Security Systems B.V.