A6" Indoor Unit: Fan Motor (M1F) Lock, Overload - Daikin RXYQ72 Serivce Manual

R-410a heat pump 60hz
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
"A6" Indoor Unit:
2.4
A6
Remote
Controller
Display
Applicable
All indoor unit models
Models
Method of
Detection by failure of signal for detecting number of turns to come from the fan motor
Malfunction
Detection
Malfunction
When number of turns can't be detected even when output voltage to the fan is maximum
Decision
Conditions
Supposed
Causes
Troubleshooting
124
Fan Motor (M1F) Lock, Overload
Fan motor lock
Disconnected or faulty wiring between fan motor and PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Is the
wiring from the fan
motor securely connected
to connectors on the
indoor unit PC
board?
YES
Wiring
between the
indoor unit PC board and
fan motor is
disconnected.
NO
Does the fan motor run?
NO
NO
YES
YES
SiUS39-601
Connect the wiring and turn on
again.
Fix the wiring and turn on again.
Replace the indoor unit PC board.
Replace the fan motor.
(V2779)