RRP: Port module card (UPM and XPM)

Tools required
Removal
218
SAN140M Installation and Service Manual
b. Click the Sys Err Light tab. The Switch page displays with
the Sys Err Light tab selected. A System Error Light is ON
message displays on the page.
c. Click Clear Light.
17. If necessary, close and lock the equipment cabinet door.
Use the following procedures to remove or replace a UPMor XPM
(port) card. A list of tools required is provided.
The following tools are required to perform these procedures.
Door key with 5/16-inch socket (provided with the equipment
cabinet).
ESD grounding cable and wrist strap.
Torque tool and hex adapter (provided with the director).
Fiber-optic protective plugs (provided with the director).
Protective caps (provided with fiber-optic jumper cables).
Fiber-optic cleaning kit.
To remove a port card:
1. Notify the customer that all ports on the defective port card will
be blocked. Ensure the customer system administrator quiesces
Fibre Channel frame traffic through any operational ports on the
card and sets attached devices offline.
2. If the director is installed in a stand-alone configuration, go to
step
4. If the director is rack-mounted, perform one of the
following:
— If the director is installed in an equipment cabinet, insert the
5/16" door tool into the socket hole at the right top of the rear
door. Turn the tool counter-clockwise to unlock and open the
door.
— If the director is installed in a customer-supplied equipment
cabinet, unlock and open the cabinet rear door as directed by
the customer representative.
3. To remove a rear-mounted FRU, remove the RFI shield.