Basic Troubleshooting

FQ2-S1
FQ2-S2
FQ2-S3
Problem
The Sensor or Touch Finder will not start. Check the power supply capacity to see if it is sufficient.
The Sensor cannot be detected.
The Setup Mode display opens.
The judgement result JG is -15 (out of
range error) during measurement.
"Touch Finder setting version error"
appears when switching Sensors or
switching between the Run Mode and
Setup Mode displays at startup (Sensor
software version 1.91 or later).
The results display is not updated.
Updating the results display is slow.
Data is not logged properly.
The ERROR indicator lights.
The measurement trigger is not input.
The image brightness does not stabilize.
(FQ2-S1@@@@@/FQ2-S2@@@@@/
FQ2-S3@@@@@/FQ2-S3@@@@@-M/
FQ2-S4@@@@@/FQ2-S4@@@@@-M/
FQ2-CH only)
FQ2-S/CH User's Manual
FQ2-S4
FQ2-CH
Measures to perform
Check the Ethernet cable to see if it is connected correctly.
Check the Ethernet settings to see if they are correct between the
devices.
If you do not know the IP address of the sensor, execute [TF settings] -
[Re-assign IP forcibly]. The sensor IP address will be assigned based on
the network settings of the computer.
Check the communications cable to see if it is disconnected.
Check the switching hubs to see if any of them are faulty. (If switching
hubs are used.)
No more than a combined total of two PC Tool / Touch Finder units can
be connected at once. If the PC Tool or Touch Finder is already con-
nected to the Sensor, disconnect it.
Check if an inspection item is set in the scene of the connected FQ.
If an inspection item is set in the scene of the connected FQ, the Run
Mode display will open at startup. If the Touch Finder is started when the
scene of the connected FQ does not have an inspection item set, the
Setup Mode display will open.
An area where the image does not exist is included in the measurement
area due to position compensation or partial input. Change the settings
so that the area where the image exists is the measurement area.
This appears when the Touch Finder software version is older than the
Sensor software version. Functions not supported by the Touch Finder
are shown as "XXX". Update the Touch Finder software to the latest ver-
sion.
Check to see if the TRIG signal is being correctly input to the Sensor.
Check to see if the most recent NG result is being displayed.
If other devices are connected to the same network as the Sensor, dis-
connect the other devices from the network and check the update
speed.
If the update speed returns to normal, check the specifications of the
disconnected devices and take suitable measures.
If there are power lines running in parallel with the Ethernet cable or if
there are inverters or other sources of noise near the communications
cable, separate the communications cable from them and check the
update speed.
Noise may be adversely affecting the communications response.
Check to see if the logging setting in the Sensor are correct.
If logging to an SD card is not possible, check the available space on the
SD card and check to see if the SD card is write-protected.
Check the error history to see what error has occurred and take suitable
measures.
Check to see it the measurement trigger is set correctly.
Turn ON the brightness correction mode.
When the Brightness Correction Mode is ON, the timing when images
are taken changes. Check that the images of the measured objects
taken when the Brightness Correction Mode is ON are appropriate.
Reference
---
---
p. 59
p. 302
---
---
---
p. 28
---
p. 419
p. 264
p. 262
---
---
p. 269
p. 280
p. 298
---
p. 67