Operator Rotation Direction Selection
•Select the rotation direction applied to the RUN command via the Digital Operator.
•This is disabled at terminals.
Parameter No.
Function name
Operator rotation direction
F004
<Group A: Standard Function Parameters>
Frequency Reference Selection
Select the method for using the frequency reference.
Parameter No.
Function name
Frequency reference
A001
selection
Related functions
Data
Set a frequency with the FREQ adjuster on the Digital Operator.
00
(Enabled when 3G3AX-OP01 is used.)
01
Set a frequency via terminals. (FV-FC, FI-FC, FE-FC)
02
Set a frequency via the Digital Operator (F001).
03
Set a frequency through the ModBus communication.
04
Set a frequency via the PCB mounted to option port 1.
05
Set a frequency via the PCB mounted to option port 2.
06
Set a frequency as a pulse train by using 3G3AX-PG01.
07
Not used
10
The operation result of the frequency operation function is defined as a frequency reference.
00: Forward
selection
01: Reverse
00: Digital Operator (FREQ adjuster)
01: Terminal
02: Digital Operator (F001)
03: ModBus communication
04: Option 1
05: Option 2
06: Pulse train frequency
07: Not used
10: Operation function result
Frequency reference source
Data
Default setting
Data
Default setting
A005, A141 to A143, A145, A146
4-2 Function Mode
Unit
⎯
00
Unit
⎯
02
4-10
4