4-2 Function Mode
Parameters Required for Brake Control Function
Parameter No.
b120
b121
b122
4
b123
b124
b125
Brake release frequency
b126
b127
Related functions
*1. Set a brake release frequency higher than the starting frequency (b082).
*2. If the set current is too low, sufficient torque may not be provided when the brake is released.
In any of the following cases, the Inverter trips and outputs the brake error signal (BER). (Brake error:
E36)
•The output current is lower than the release current after the brake release establishment wait time
(b121) elapses.
• When the brake confirmation (BOK) signal is used, the brake confirmation signal does not turn on
within the brake confirmation wait time (b124) during acceleration, or does not turn off within the
brake confirmation wait time (b124) during deceleration; or the brake confirmation signal turns off,
although the brake release signal is output.
4-75
Function name
00: Disabled
Brake control selection
01: Enabled
0.00 to 5.00:
Brake wait time for
Set a time required for the output current to
release
reach the rate of the release current after
reaching the release frequency.
0.00 to 5.00:
Brake wait time for
Set a mechanical delay time from when the
acceleration
release signal is output until the brake is
released.
0.00 to 5.00:
Brake wait time for
Set a mechanical delay time from when the
stopping
release signal is turned off until the brake is
closed.
0.00 to 5.00:
Set a wait time longer than the time from
Brake wait time for
when the release signal is released until the
confirmation
brake outputs the release completion signal
to the Inverter.
0.00 to 99.99/100.0 to 400.0 (Hz):
Set a frequency to output the brake release
signal.
0 × Rated current to 2.0 × Rated current:
Brake release current
Set an output current that allows the brake to
be released.
0.00 to 99.99/100.0 to 400.0:
Brake input frequency
Set a frequency to close the brake during
stop.
Data
*1
*2
*1
C001 to C008, C021 to C025
Default setting
Unit
00
0.00
s
0.00
s
0.00
s
0.00
s
0.00
Hz
Rated current
0.00
Hz